+32 56 77 47 50
IRD
Airdiff

Iris Damper

Ref: IRD

Precision iris damper with built-in measuring station for quick airflow measurement and balancing in round ducts.

Key Specifications

Body material
Galvanised steel
Blade material
Stainless steel
Available diameters
Ø 100 – Ø 400 mm
Max velocity
15 m/s
Measuring accuracy
± 5 %
Temperature range
–30 °C to +80 °C

Description

The IRD iris damper combines a variable iris aperture with an integrated differential-pressure measuring station, enabling accurate airflow measurement and regulation in a single device. By reading the differential pressure across the iris with a standard manometer, the installer can determine the actual airflow and adjust the opening to match the design value — all without additional balancing tools. The iris mechanism provides a near-circular orifice at all positions, minimising turbulence and regenerated noise.

Features

  • Integrated differential-pressure measuring station
  • Near-circular iris aperture
  • External adjustment handle with locking ring
  • Low regenerated noise
  • Calibrated flow chart supplied

Applications

  • Round duct airflow balancing
  • Laboratory exhaust regulation
  • Cleanroom supply air

Technical Documents

Materials

Galvanised steel bodyStainless steel iris blades